YMGI VRF Heat Pump -4°F Series


AboutFeaturesMini 36, 48K & 60 Btu/h SpecificationsModular 72 Btu/h SpecificationsModular 96 & 120K Btu/h SpecificationsDownloads

YMGI VRF -4°F Heat Pump Series Mini & Modular

A FLEXIBLE AND AFFORDABLE VRF SYSTEM

YMGI’s VRF Heat Pump system is designed to deliver comfort year round. Effective in a wide range of outdoor ambient temperatures (as low as -4°F), YMGI VRF Heat Pump systems can meet all your heating and cooling needs, with no need for a supplemental heating system in certain climates. YMGI VRF systems can replace traditionally designed
gas furnace and AC/HP coil & outdoor unit systems and save money on installation and operation.

What is Variable Refrigerant Flow?


Variable Refrigerant Flow, or VRF technology, is a heating and cooling system that routes 2 or 3-pipe refrigerant circuits from one outdoor unit to multiple indoor units (or zones) and can provide heating and cooling at the same time in different zones. A Heat pump only VRF system (2 pipe circuit) supply heating or cooling multiple zones but all zones must be in heat or cool mode at the same time. A Heat Recovery VRF system (3 pipe circuit) can supply heating and cooling to multiple zones at the same time.

Traditional refrigerant systems are either “on” and operating at 100% capacity or “off”. VRF systems use inverter compressor technology, which provide variable speed operation. Why is this so important? Because your HVAC systems seldom needs to provide 100% of the capacity they are designed for. Operating at such extremes can lead to premature component or system failure.

VRF systems routinely operate at partial loads in the range of 30 to 70% which provides more consistent indoor temperatures and humidity levels, and energy efficiency.

Because of this partial-load capability, VRF systems are often more efficient, than commercial chiller/boiler systems while at the same time offering much greater design flexibility while using much less installation space.

Contractor Selection is Very Important

To get the efficiency, durability, and superior control these systems are designed for, the piping and control systems must be installed according to the manufacturers’ very precise instructions. VRF systems are complex, and to ensure proper operation and longevity, all installations must be performed by  licensed HVAC professional trained in VRF system installation.

Start-up and commissioning should be performed only by a manufacturer certified commissioning agent, which may be a qualified contractor, manufacturer’s representative, or manufacturer’s employee. VRF manufacturers limit and void their warranties on systems not properly installed and commissioned.

YMGI VRF Advantages

  • Efficiency: VRF systems are better than chillers and much more efficient than standard splits and RTU’s.
  • VRF Systems can be installed in a smaller area, due to its smaller footprint, equipment takes up less square footage.
  • Individual room control: indoor units can heat and cool independently.
  • Durability: VRF Systems are designed to withstand harsh environments and operate for years. These systems have also been outlasting chillers.
  • Excellent de humidification, which is great for building preservation.
  • Design flexibility: wall mounted, ceiling mounted, concealed non-ducted cassettes fit in frames for acoustical ceiling tiles, and concealed ducted indoor units.
  • Very low maintenance (particularly when compared to central systems).
  • Modular installation: these systems are great for retrofits, adding additional tonnage, and phased construction.
  • No gas required; all electric. No auxiliary heat strips needed.
  • Suitable for a broad geographical range. These systems perform to subzero temperatures (-22°F).

More Installation Options

SOLAR SERIES VRF systems offer a variety of Indoor Unit options. If you’re doing a retrofit, the SOLAR SERIES VRF can use our ducted Indoor Units and bolt onto existing duct work. For new construction, we offer 4 different Indoor Units that allow you to go ductless, giving building occupants the flexibility to control their comfort at whatever level they would like in the room they are occupying.

Benefits

Energy efficiency.
VRF systems use less energy for several reasons. The system is designed to provide exactly the amount of cooling needed for the current conditions, which means it runs less frequently and at a lower capacity. VRF Heat Recovery systems are also designed to capture heat from the cooling process and reuse it in other areas that may need heating.

Quiet operation.
In a VRF system, the noisier condensing unit is typically outside, and the indoor air handlers are smaller and quieter than a traditional split system.

Heat and cool simultaneously.
The VRF Heat Recovery system captures residual heat absorbed from the air during the cooling process, and redirects that heat to other parts of the building that need heat. That means you can have air conditioning in the living room for a party, while you heat the bedroom where the baby is sleeping. Or you can have heat in the winter for cooler window offices, and air conditioning in the central conference room for a large meeting.

Consistent comfort.
The VRF system’s compressor can detect the precise requirements of each zone, and send the exact amount of refrigerant needed to do the job. As a result, each area is consistently comfortable with well-controlled humidity, and no hot or cold spots.

Less Downtime.
Since the VRF system is designed to run only when needed and under partial-load conditions, there is less wear and tear on the parts. That means fewer breakdowns. Also, if something goes wrong with one air handler, often the others are unaffected. That means your whole space won’t be without air conditioning all at once.

Requires Less Installation space.
Since the air handlers are smaller and VRF systems don’t usually require ducts, they don’t require as much wall and ceiling space for the equipment. That means you get to keep those gorgeous high ceilings in your apartment.

Modern Controls.
For residences, you can take advantage of mobile control technology that lets you adjust temperature settings for each zone from your mobile device. For commercial settings, the VRF system’s built-in controls may allow you to skip purchasing expensive building management software.

Let’s not forget maintenance

Like other HVAC systems, VRF systems do need to be regularly inspected and maintained by a professional. With such a sophisticated system, you want to be sure to choose a provider with the right experience, and who can design a maintenance contract based on the needs of your system.

Model  Unit VRFO-36HP-V2B(55)5 VRFO-48HP-V2B(55)5 VRFO-60HP-V2B(55)5
Cooling Capacity Btu/h 36,000 48,000 60,000
EER Ducted 11.30 9.50 9.30
Mixed Ducted 12.15 11.00 10.50
Non-Ducted 13.00 12.50 12.00
SEER Ducted 16.50 16.50 16.00
Mixed Ducted 18.50 18.25 17.75
Non-Ducted 20.50 20.00 19.50
Heating
Capacity
Btu/h 45,000 54,000 66,000
HSPF Ducted 10.30 10.20 9.70
Mixed Ducted 11.00 10.60 10.10
Non-Ducted 11.70 11.00 10.50
Air
flow volume
CFM 3531 3531 4590
Heating
Capacities at Different OD
Ambient Temperatures
47 °F 100% / 45,000 100% / 54,000 100% / 66,000
17 °F 100% / 45,000 100% / 54,000 100% / 66,000
-4 °F 100% / 45,000 100% /54,000 100% / 66,000
Sound
Pressure Level
dB 56 57 63
Power
Supply
V/Ø/Hz 208~230/1/60 208~230/1/60 208~230/1/60
Power
Input Cooling
Ducted kW 3.2 4.45
Ductless kW 2.7 4.35 6.45
Power
Input Heating
Ducted kW 3.95 4.65
Ductless kW 3.3 4.40 5.60
MCA A 37 37 37
MOP A 50 50 50
Connection
Method
Flare Connection Flare Connection Flare Connection
Refrigerant R410A R410A R410A
Compressor
Manufacturer
GR/LD GR/LD GR/LD
Compressor
Type
Two-stage Variable Frequency Rotary Two-stage Variable Frequency Rotary Two-stage Variable Frequency Rotary
Compressor
Quantity
No. 1 1 1
Motor
Type
INVERTER INVERTER INVERTER
Fan
Quantity
2 2 2
Capacity
Adjustment Range
%~% 15%~120% 15%~120% 15%~120%
Maximum drive IDU NO. unit 5 7 13
Max.
Equivalent Connection Pipe Length
feet 360 360 540
Condenser
Fin Color
Golden Golden Golden
Cooling
Operation Ambient Temperature Range
°F 23° ~ 118° 23° ~ 118° 23° ~ 118°
Heating
Operation Ambient Temperature Range
°F -4° ~ 80.6° -4° ~ 80.6° -4° ~ 80.6°
Refrigerant
Charge
oz 176.4 176.4 176.4
Low
Ambient Cooling Function
YES YES YES
Outer
Diameter Liquid Pipe
in. 3/8 3/8 3/8
Outer
Diameter Gas Pipe
in. 5/8 5/8 3/4
Net
Weight
lbs 242.6 242.6 273.4
Base
Pan Heater
YES YES YES
Model Unit VRFO-72HP-V2C(55)5
Cooling Capacity Btu/h 69,000
Heating Capacity Btu/h  77,000
Air flow volume CFM 6700
ESP WC 0.33”
Heating Capacities at Different OD
Ambient Temperatures
47 °F 100% /81,000
17 °F 100% / 81,000
-4 °F 100% / 81,000
EER
Ducted / Mixed / Non-Ducted
11.10 / 12.40 / 13.70
IEER
Ducted / Mixed / Non-Ducted
21.50 / 24.80 / 28.10
COP
47  Ducted / Mixed / Non-Ducted
3.40 / 3.81 / 4.22
COP
17  Ducted / Mixed / Non-Ducted
2.40 / 2.46 / 2.51
Sound
Pressure/ Power Level
dB 61/71
Power Supply V/Ø/Hz 208~230/3/60
Power
Input Cooling
Ducted kW
Ductless kW 5.45
Power
Input Heating
Ducted kW
Ductless kW 5.80
MCA A 40
MOP/HVAC Circuit Breaker A 60
Connection Method Brazing
Outer Diameter Liquid Pipe in. 3/8
Outer Diameter Gas Pipe in. 7/8
R410A Refrigerant Factory Charge oz 236
Compressor Manufacturer Hitachi
Compressor Type Inverter Scroll Hermetic
Compressor Quantity No. 1
Motor Type Permanent Magnet
Synchronous Motor
Fan Quantity/Type 1 Axial
Capacity Adjustment Range %~% 12%~120%
Maximum No. of drive IDU units 16
IDU Capacity Total % ODU 50-150% zoning
Condenser Fin Color Gold
Cooling Operation Ambient Temperature Range °F 23° ~ 126°
Net Weight lbs 496
Heating Operation Ambient Temperature Range °F -4° ~75°
Base Pan Heater YES
Model Unit VRFO-96VP-V2C(55)5 VRFO-120VP-V2C(55)5
Cooling Capacity Btu/h 92,000 114,000
Heating Capacity Btu/h 103,000 129,000
Air flow volume CFM 8240 8240
ESP WC 0.33” 0.33”
Heating Capacities at Different OD Ambient Temperatures 47 °F 100% / 103,000 100% / 129,000
17 °F 100% / 103,000 100% / 129,000
-4 °F 100% / 103,000 100% / 129,000
EER
Ducted / Mixed / Non-Ducted
11.20 / 12.20 /13.20 11.20 / 11.80 / 12.40
IEER
Ducted / Mixed / Non-Ducted
 20.00 / 23.30 / 26.60 22.30 / 23.75 / 25.20
COP
47  Ducted / Mixed / Non-Ducted
3.40 / 3.78 / 4.15 3.95 / 3.63 / 3.30
COP
17  Ducted / Mixed / Non-Ducted
2.38 / 2.44 / 2.50 2.30 / 2.36 / 2.41
Sound
Pressure/ Power Level
dB 61 / 72 61 / 72
Power Supply V/Ø/Hz 208~230/3/60 208~230/3/60
Power
Input Cooling
Ducted kW
Ductless kW 7.30 9.58
Power
Input Heating
Ducted kW
Ductless kW 7.85 10.42
MCA A 45 45
MOP/HVAC Circuit Breaker A 70 70
Connection Method Brazing Brazing
Outer Diameter Liquid Pipe in. 3/8 3/8
Outer Diameter Gas Pipe in. 7/8 7/8
R410A Refrigerant Factory Charge oz 345 345
Compressor Manufacturer Hitachi Hitachi
Compressor Type Inverter Scroll Hermetic Inverter Scroll Hermetic
Compressor Quantity No. 2 2
Motor Type Permanent Magnet Synchronous Motor Permanent Magnet Synchronous Motor
Fan Quantity/Type 2 Axial 2 Axial
Capacity Adjustment Range %~% 12%~120% 12%~120%
Maximum No. of drive IDU units 23 23
IDU Capacity Total % ODU 50-150% zoning 50-150% zoning
Condenser Fin Color Gold Gold
Cooling Operation Ambient Temperature Range °F 23° ~ 126° 23° ~ 126°
Heating Operation Ambient Temperature Range °F -4° ~75° -4° ~75°
Net Weight lbs 793 793
Base Pan Heater YES YES